7.4.3 Electrical
Connections
Function
Terminal
TC
RTD
POT
V
mA
mA
Loop
Terminal
Function
Connector
11
+
3W / 4W
41
Out
12
– / CJC
2W / 3W / 4W
M3
42
Out +
output
13
CJC
2W /3W / 4W
M1
43
COM
14 4W
M2
44
NO
output
relay
21
–
–
51
+24 V DC
22
+
–
52
GND
power
supply
23
+
53
NC
24
+ 54 COM
status
relay
Table 7-8: Electrical Connections
7.4.4 Specifications
Features
Configuration and monitoring via FDT/DTM-Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,
2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.
The active or passive signal inputs for RTD, TC, potentiometer, V and mA are completely electrically
isolated.
The device detects automatically whether an active or passive current signal is connected.
The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11.
Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
Front LEDs indicates operation status and malfunction.
3-way galvanic isolation between input, output and power supply.