Weidmuller ACT20X User Manual
Page 33
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
1066540000/01/12.11
33
Sensor error current:
when detecting
else
< 2 μA
0 μA
TC Input, Sensor Types
Temperature Range
Standard
B
0…+1820 °C
IEC 60584-1
E
-100…+1000 °C
IEC 60584-1
J
-100…+1200 °C
IEC 60584-1
K
-180…+1372 °C
IEC 60584-1
L
-200…+900 °C
DIN 43710
N
-180…+1300 °C
IEC 60584-1
R
-50…+1760 °C
IEC 60584-1
S
-50…+1760 °C
IEC 60584-1
T
-200…+400 °C
IEC 60584-1
U
-200…+600 °C
DIN 43710
W3
0…+2300 °C
ASTM E988-90
W5
0…+2300 °C
ASTM E988-90
LR
-200…+800 °C
GOST 3044-84
Accuracy, General Values
Absolute Accuracy
Temperature Coefficient
All
≤
0.1 % of span
≤
0.01 % of span / °C
Accuracy, Basic Values
Absolute Accuracy
Temperature Coefficient
mA
≤
16 μA
≤
1.6 μA / °C
Pt100, Pt200, Pt1000
≤
0.2 °C
≤
0.02 C / °C
Pt500, Ni100, Ni120, Ni1000
≤
0.3 °C
≤
0.03 C / °C
Pt50, Pt400, Ni50
≤
0.4 °C
≤
0.04 C / °C
Pt250, Pt300
≤
0.6 °C
≤
0.06 C / °C
Pt20
≤
0.8 °C
≤
0.08 C / °C
Pt10
≤
1.4 °C
≤
0.14 C / °C
TC type: E, J, K, L, N, T, U
≤
1 °C
≤
0.1 C / °C
TC type: R, S, W3, W5, LR
≤
2 °C
≤
0.2 C / °C
TC type: B (160…400 °C)
≤
4.5 °C
≤
0.45 C / °C
TC type: B (400…1820 °C)
≤
2 °C
≤