Sensaphone 1400 User Manual
Page 120

Sensaphone 1400 Manual
118
Power Supply
Power Supply: 120VAC/9VDC 60Hz 6W wall plug-in transformer
(230VAC/9VDC 50/60Hz power supply optional)
Power Consumption: 5 Watts
Power Protection: Metal Oxide Varistor
Battery Backup: 6V 1.3 AH sealed gel cell, provides up to 24 hours
of back-up time
Environmental
Operating Temperature: 32–122 deg F (0–50 deg C)
Operating Humidity: 0–90% RH non-condensing
Storage Temperature: 32–140 deg F
Physical
Dimensions: 12.1"h x 7.3"w x 4.5"d
Weight: 5 lbs.
Enclosures:
• Solid Door Enclosure: ABS/PC Blended Plastic, UL94-5VB
Flammability rating, NEMA Type 1, 2, 3, 3R, 4, 4X, 12 & 13,
IEC529, IP66.
• Clear Door Enclosure: ABS/PC blended plastic, UL94–5VB
flammability rating; UV stabilized. NEMA Type 1, 2, 3, 3R, 4, 4X,
12 &13, IEC529–IP65.
Standards
- FCC Part 15 Class A, USA Emission Standards
- FCC Part 68 (47 C.F.R. Part 68), USA Telecommunications
Standards
- ICES-003 Issue 4 Class A, Canadian Emission Standards
- Complies with CS-03 Issue 8, Canadian Telecommunications
Standards
- NRTL Listed for compliance to UL60950-1, USA Safety Standards
- NRTL Listed for compliance to CSA C22.2 No. 60950-1,
Canadian Safety Standards
Specifications subject to change