Chapter 5 Configuring the PM135
Configuring Billing/TOU
98
PM135 Powermeter Series
5.4 Configuring Billing/TOU
The TOU battery-backed clock unit is highly recommended in case
of using time-scheduled tariff rates, otherwise a long power
outage may cause the meter clock to lose time so your tariff
counters would not comply with the calendar schedule.
Billing Energy Registers
The PM135E/EH has 4 fully programmable billing energy registers that
can be linked to any internal energy source or to an external pulse source
that delivers pulses through the meter digital inputs.
Any energy register can provide either a single-tariff energy accumulation
or be individually linked to the TOU system providing both total and multi-
tariff energy billing.
Tariff Rates
The meter tariff structure supports 8 different tariff rates using an
arbitrary tariff schedule. A total of 4 types of days and 4 seasons are
supported with up to eight tariff changes per day.
Maximum Demand Registers
Any of billing energy registers can be individually linked to the maximum
demand register providing the same demand tariff structure as you
selected for energy registers.
Recording Billing Data and Load Profiling
The PM135E/EH can provide automatic recording of the daily energy and
maximum demand profile to a data log file. Maximum demand profiling
can be individually configured for every register.
in Appendix E for more information on the file layout and contents.
To configure the billing registers and the tariff system in your
meter:
1. Link the billing registers to the
respective energy sources.
2. Configure the options for the
registers to whether the only
totalization or both total and tariff
registers would be used, and
whether daily profiling should be
enabled for the energy usage and
maximum demand registers.
3. Configure the daily tariff schedule
using the TOU daily profiles for all
types of days and seasons.
4. Configure the season tariff schedule
using the TOU calendar.
Configuring Billing/Tariff Registers
To configure the billing/TOU registers in your meter:
1. Select Energy/TOU from the
Meter Setup menu.