Bryant PACKAGED HEAT PUMP 548J User Manual
Page 9

9
Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT
UNIT
COOLING
ELECTRIC HEATERS
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
548J*04
900
1500
900
1500
548J*05
1200
2000
1200
2000
548J*06
1500
2500
1500
2500
548J*07
1800
3000
1800
3000
548J*08
2250
3750
2250**
3750
548J*09
2550
4250
2250**
4250
**Minimum electric heat CFM exceptions :
UNIT
UNIT VOLTAGE
HEATER kW
UNIT
CONFIGURATION
REQUIRED MINIMUM
CFM
548J*08
548J*09
575
17.0
Horizontal or Vertical
2800
34.0
2350
Table 4 – SOUND PERFORMANCE TABLE
548J*
OUTDOOR SOUND (DB)
A---WEIGHTED
63
125
250
500
1000
2000
4000
8000
04A
77
78.9
81.7
74.9
72.5
70.3
65.6
65.6
62.6
05A
80
90.4
84.6
77.6
77.5
74.8
70.6
68.0
64.2
06A
80
92.7
84.9
79
76.7
73.8
69.6
66.4
62.8
07A
78
88.0
79.5
76.2
75.8
72.5
68.6
65.7
62.4
08D
82
89.7
81.5
80.5
79.2
77.1
73.2
70.2
67.4
09D
84
90.8
85.2
81.6
79.5
78.1
74.0
70.4
66.5
LEGEND
dB --- Decibel
NOTES:
1. Outdoor sound data is measure in accordance with ARI stand-
ard 270---95.
2. Measurements are expressed in terms of sound power. Do not
compare these values to sound pressure values because sound
pressure accounts for specific environmental factors which do
not match individual applications. Sound power values are inde-
pendent of the environment and therefore more accurate.
3. A---weighted sound ratings filter out very high and very low
frequencies, to better approximate the response of an “aver-
age” human ear. A---weighted measurements for Bryant units
are taken in accordance with 270---95.
548J