beautypg.com

Sequence of operation – Bryant PACKAGED HEAT PUMP 548J User Manual

Page 66

background image

66

SEQUENCE OF OPERATION

Cooling, unit without economizer

When thermostat calls for cooling, terminals G and Y1 are

energized. The indoor-fan contactor (IFC), reversing valve

solenoid (RVS) and compressor contactor are energized

and indoor-fan motor, compressor, and outdoor fan starts.

The outdoor fan motor runs continuously while unit is

cooling.

Heating, unit without economizer

Upon a request for heating from the space thermostat,

terminal W1 will be energized with 24V. The IFC,

outdoor-fan contactor (OFC), C1, and C2 will be

energized. The indoor fan, outdoor fans, and compressor

no. 1, and compressor no. 2 are energized and reversing

valves are deenergized and switch position.

If the space temperature continues to fall while W1 is

energized, W2 will be energized with 24V, and the heater

contactor(s) (HC) will be energized, which will energize

the electric heater(s).

When the space thermostat is satisfied, W2 will be

deenergized first, and the electric heater(s) will be

deenergized.

Upon a further rise in space temperature, W1 will be

deenergized.

Cooling, unit with EconoMi$er IV

When free cooling is not available, the compressors will

be controlled by the zone thermostat. When free cooling is

available, the outdoor-air damper is modulated by the

EconoMi$er IV control to provide a 50 to 55_F (10_ to

13_C) mixed-air temperature into the zone. As the

mixed-air temperature fluctuates above 55 or below 50_F

(13_ to 10_C), the dampers will be modulated (open or

close) to bring the mixed-air temperature back within

control.

If mechanical cooling is utilized with free cooling, the

outdoor-air damper will maintain its current position at

the time the compressor is started. If the increase in

cooling capacity causes the mixed-air temperature to drop

below 45_F (7_C), then the outdoor-air damper position

will be decreased to the minimum position. If the

mixed-air temperature continues to fall, the outdoor-air

damper will close. Control returns to normal once the

mixed-air temperature rises above 48_F (9_C).

If optional power exhaust is installed, as the outdoor-air

damper opens and closes, the power exhaust fans will be

energized and deenergized.

If field-installed accessory CO

2

sensors are connected to

the EconoMi$er IV control, a demand controlled

ventilation strategy will begin to operate. As the CO

2

level in the zone increases above the CO

2

setpoint, the

minimum position of the damper will be increased

proportionally. As the CO

2

level decreases because of the

increase in fresh air, the outdoor-air damper will be

proportionally closed.

For EconoMi$er IV operation, there must be a thermostat

call for the fan (G). If the unit is occupied and the fan is

on, the damper will operate at minimum position.

Otherwise, the damper will be closed.

When the EconoMi$er IV control is in the occupied mode

and a call for cooling exists (Y1 on the thermostat), the

control will first check for indoor fan operation. If the fan

is not on, then cooling will not be activated. If the fan is

on, then the control will open the EconoMi$er IV damper

to the minimum position.

On the initial power to the EconoMi$er IV control, it will

take the damper up to 2

1

/

2

minutes before it begins to

position itself. Any change in damper position will take

up to 30 seconds to initiate. Damper movement from full

closed to full open (or vice versa) will take between 1

1

/

2

and 2

1

/

2

minutes.

If free cooling can be used as determined from the

appropriate changeover command (switch, dry bulb,

enthalpy curve, differential dry bulb, or differential

enthalpy), then the control will modulate the dampers

open to maintain the mixed-air temperature setpoint at

50_ to 55_F (10_ to 13_C).

If there is a further demand for cooling (cooling second

stage — Y2 is energized), then the control will bring on

compressor stage 1 to maintain the mixed-air temperature

setpoint. The EconoMi$er IV damper will be open at

maximum position. EconoMi$er IV operation is limited to

a single compressor.

Heating, unit with EconoMi$er

When the room temperature calls for heat through

terminal W1, the indoor (evaporator) fan contactor (IFC)

and heater contactor no. 1 (HC1) are energized and the

reversing valve(s) deenergize and switches position. On

units equipped for 2 stages of heat, when additional heat is

needed, heater contactor no. 2 is energized through W2.

The economizer damper moves to the minimum position.

When the thermostat is satisfied, the damper moves to the

fully closed position.

Defrost

When the temperature of the outdoor coil drops below

28_F (--2_C) as sensed by the defrost thermostat (DFT2)

and the defrost timer is at the end of a timed period

(adjustable at 30, 60, 90 or 120 minutes), reversing valve

solenoids (RVS1 and RVS2) are energized and the OFC is

deenergized. This switches the position of the reversing

valves and shuts off the outdoor fan. The electric heaters

(if installed) will be energized.

The unit continues to defrost until the coil temperature as

measured by DFT2 reaches 65_F (18_C), or the duration

of defrost cycle completes a 10-minute period.

During the Defrost mode, if circuit 1 defrosts first, RVS1

will oscillate between Heating and Cooling modes until

the Defrost mode is complete.

548J