Table 2 – ARI COOLING RATING TABLES
COOLING MODE
548J*
NOMINAL
CAPACITY
(TONS)
NET COOLING
CAPACITY
(BTUH)
TOTAL
POWER
(kW)
SEER
EER
IPLV
04A
3
37,000
3.3
13.40**
11.00
N/A
05A
4
47,000
4.1
13.10**
11.20
N/A
06A
5
61,500
5.5
13.20**
11.15
N/A
07A
6
70,000
6.3
N/A
11.10
N/A
08D
7.5
88,000
7.8
N/A
11.20
12.40
09D
8.5
99,000
8.8
N/A
11.20
12.40
NOTE:
All AHRI ratings are based on 230, 460 and 575 volt.
**
Electric Drive (direct drive) X13 5 speed/torque motor. SEER rating is 13.0 for belt drive.
NA Not applicable
HEATING MODE
548J*
HSPF
HEATING, LOW
HEATING, HIGH
CAPACITY
(BTUH)
COP
CAPACITY
(BTUH)
COP
04A
7.70
18,200
N/A
35,600
N/A
05A
7.70
23,600
N/A
45,500
N/A
06A
7.70
31,200
N/A
58,000
N/A
07A
N/A
34,800
2.25
67,000
3.30
08D
N/A
48,000
2.25
86,000
3.30
09D
N/A
54,500
2.25
96,000
3.30
LEGEND
ARI
--- Air---Conditioning, Heating and Refrigeration
Institute
ASHRAE
--- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
COP
--- Coefficient of Performance
EER
--- Energy Efficiency Ratio
HSPF
--- Heating Seasonal Performance Factor
IPLV
--- Integrated Part Load Value
SEER
--- Seasonal Energy Efficiency Ratio
This product has been designed and manufactured to
meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air flow
are critical to achieve rated capacity and efficiency.
Installation of this product should follow all
manufacturer’s refrigerant charging and air flow
instructions.
Failure to confirm proper charge and
air flow may reduce energy efficiency and shorten
equipment life.
NOTES:
1. Rated and certified under ARI Standard 210/240---06 or
340/360---07, as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air
temp and 95_F db outdoor air temp.
IPLV Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air
temp and 80_F (27_C) db outdoor air temp.
3. All 548J units comply with ASHRAE 90.1 2001, 2004 Energy
Standard for minimum SEER and EER requirements.
4. Where appropriate, 548J units comply with US Energy Policy
Act (2005). Refer to state and local codes or visit the following
website: http://bcap---energy. org to determine if compliance
with this standard pertains to your state, territory, or
municipality.