Table 2 – ARI COOLING RATING TABLES

COOLING MODE

548J*

NOMINAL

CAPACITY

(TONS)

NET COOLING

CAPACITY

(BTUH)

TOTAL

POWER

(kW)

SEER

EER

IPLV

04A

3

37,000

3.3

13.40**

11.00

N/A

05A

4

47,000

4.1

13.10**

11.20

N/A

06A

5

61,500

5.5

13.20**

11.15

N/A

07A

6

70,000

6.3

N/A

11.10

N/A

08D

7.5

88,000

7.8

N/A

11.20

12.40

09D

8.5

99,000

8.8

N/A

11.20

12.40

NOTE:

All AHRI ratings are based on 230, 460 and 575 volt.
**

Electric Drive (direct drive) X13 5 speed/torque motor. SEER rating is 13.0 for belt drive.

NA Not applicable

HEATING MODE

548J*

HSPF

HEATING, LOW

HEATING, HIGH

CAPACITY

(BTUH)

COP

CAPACITY

(BTUH)

COP

04A

7.70

18,200

N/A

35,600

N/A

05A

7.70

23,600

N/A

45,500

N/A

06A

7.70

31,200

N/A

58,000

N/A

07A

N/A

34,800

2.25

67,000

3.30

08D

N/A

48,000

2.25

86,000

3.30

09D

N/A

54,500

2.25

96,000

3.30

LEGEND

ARI

--- Air---Conditioning, Heating and Refrigeration

Institute

ASHRAE

--- American Society of Heating, Refrigerating

and Air Conditioning, Inc.

COP

--- Coefficient of Performance

EER

--- Energy Efficiency Ratio

HSPF

--- Heating Seasonal Performance Factor

IPLV

--- Integrated Part Load Value

SEER

--- Seasonal Energy Efficiency Ratio

This product has been designed and manufactured to

meet Energy Star® criteria for energy efficiency.

However, proper refrigerant charge and proper air flow

are critical to achieve rated capacity and efficiency.

Installation of this product should follow all

manufacturer’s refrigerant charging and air flow

instructions.

Failure to confirm proper charge and

air flow may reduce energy efficiency and shorten

equipment life.

NOTES:

1. Rated and certified under ARI Standard 210/240---06 or

340/360---07, as appropriate.

2. Ratings are based on:

Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air

temp and 95_F db outdoor air temp.

IPLV Standard: 80_F (27_C) db, 67_F (19_C) wb indoor air

temp and 80_F (27_C) db outdoor air temp.

3. All 548J units comply with ASHRAE 90.1 2001, 2004 Energy

Standard for minimum SEER and EER requirements.

4. Where appropriate, 548J units comply with US Energy Policy

Act (2005). Refer to state and local codes or visit the following

website: http://bcap---energy. org to determine if compliance

with this standard pertains to your state, territory, or

municipality.