At the end of the defrost cycle, the electric heaters (if

installed) will be deenergized; the reversing valves switch

and the outdoor-fan motor will be energized. The unit will

now operate in the Heating mode.

If the space thermostat is satisfied during a defrost cycle,

the unit will continue in the Defrost mode until the time or

temperature constraints are satisfied.

Automatic changeover

When the system selection switch is set at AUTO.

position, unit automatically changes from heating

operation to cooling operation when the temperature of

the conditioned space rises to the cooling level setting.

When the temperature of the conditioned space falls to the

heating level setting, unit automatically changes from

cooling to heating operation (with a 3°F deadband in

between).

Continuous air circulation

Turn unit power on. Set system control at OFF position.

Set fan switch at ON position. The indoor-fan contactor is

energized through the thermostat switch and the indoor

fan runs continuously.

Cycle-LOCprotection

If unit operation is interrupted by an open high-pressure

switch, low-pressure switch, indoor coil freeze stat, or by

compressor internal line-break device (overcurrent or

overtemperature), and compressor is calling for either

cooling or heating, Cycle-LOC protection device

simultaneously locks out unit and lights a warning light on

the thermostat. Restart the unit by manually turning

thermostat to OFF and then to ON position. If any of the

protective devices opens again, the unit continues to lock

out until corrective action is taken.
NOTE: If the unit fails to operate due to compressor

over-current condition, restart by manually resetting
circuit breakers at the unit. Restart cannot be
accomplished at the room thermostat.

Emergency heat

If compressor is inoperative due to a tripped safety device

(high or low pressure, indoor coil freeze stat, overcurrent,

or overtemperature), the Cycle-LOC device locks out the

compressor and lights a warning light on the room

thermostat. When the switch is on (thermostat is set to the

EM HT position), compressor circuit and outdoor

thermostats are bypassed, and the second stage of

thermostat energizes the indoor blower and the electric

resistance heaters.