Fan performance (cont.) – Bryant PACKAGED HEAT PUMP 548J User Manual
Page 37
37
FAN PERFORMANCE (cont.)
Table 23 – 548J*05 ELECTRIC DRIVE, X13 MOTOR,
4 TON HORIZONTAL SUPPLY
SPEED
(TORQUE)
TAP
CFM
ESP
BHP
1
1200
0.75
0.48
1300
0.63
0.46
1400
0.48
0.44
1500
0.33
0.41
1600
0.19
0.39
1700
0.05
0.36
1800
---
---
1900
---
---
2000
---
---
2
1200
0.97
0.58
1300
0.88
0.59
1400
0.77
0.59
1500
0.64
0.59
1600
0.50
0.57
1700
0.36
0.54
1800
0.21
0.52
1900
0.06
0.49
2000
---
---
3
1200
0.98
0.59
1300
0.91
0.60
1400
0.82
0.62
1500
0.71
0.62
1600
0.58
0.61
1700
0.45
0.60
1800
0.31
0.58
1900
0.16
0.56
2000
0.03
0.52
4
1200
0.98
0.59
1300
0.92
0.62
1400
0.86
0.64
1500
0.79
0.66
1600
0.70
0.68
1700
0.62
0.70
1800
0.52
0.71
1900
0.37
0.69
2000
0.21
0.67
5
1200
1.02
0.60
1300
0.97
0.64
1400
0.92
0.67
1500
0.87
0.71
1600
0.82
0.75
1700
0.77
0.79
1800
0.71
0.84
1900
0.65
0.88
2000
0.58
0.92
Table 24 – 548J*05 ELECTRIC DRIVE, X13 MOTOR,
4 TON VERTICAL SUPPLY
SPEED
(TORQUE)
TAP
CFM
ESP
BHP
1
1200
0.50
0.39
1300
0.36
0.37
1400
0.19
0.35
1500
0.10
0.33
1600
0.02
0.32
1700
---
---
1800
---
---
1900
---
---
2000
---
---
2
1200
0.80
0.55
1300
0.69
0.55
1400
0.50
0.54
1500
0.38
0.52
1600
0.24
0.50
1700
0.13
0.48
1800
0.01
0.46
1900
---
---
2000
---
---
3
1200
0.89
0.59
1300
0.78
0.61
1400
0.59
0.60
1500
0.46
0.58
1600
0.31
0.56
1700
0.20
0.54
1800
0.07
0.52
1900
---
---
2000
---
---
4
1200
0.89
0.60
1300
0.80
0.63
1400
0.67
0.64
1500
0.57
0.65
1600
0.43
0.65
1700
0.31
0.66
1800
0.23
0.65
1900
0.12
0.63
2000
0.01
0.62
5
1200
0.94
0.62
1300
0.85
0.65
1400
0.73
0.68
1500
0.65
0.70
1600
0.55
0.72
1700
0.47
0.75
1800
0.42
0.78
1900
0.39
0.82
2000
0.38
0.88
548J