beautypg.com

Economizer, Electric heaters – Bryant PACKAGED HEAT PUMP 548J User Manual

Page 35

background image

35

Table 20 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)

Economizer

3 --- 6 TONS

CFM (in. wg)

600

800

1000 1250 1500 1750 2000 2250 2500 2750 3000

Vertical

Economizer

0.01

0.02

0.04

0.05

0.07

0.09

0.12

0.15

0.18

0.22

0.26

Horizontal

Economizer

0.02

0.03

0.04

0.06

0.08

0.10

0.13

0.15

0.18

0.23

0.28

7.5 --- 8.5 TONS

CFM (in. wg)

2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000

Vertical

Economizer

0.06

0.08

0.09

0.12

0.13

0.15

0.17

0.20

0.22

0.25

0.29

0.33

0.36

0.40

0.44

0.48

Horizontal

Economizer

0.08

0.10

0.13

0.15

0.18

0.21

0.25

0.28

0.30

0.34

0.39

0.43

0.47

0.51

0.56

0.60

Electric Heaters

3 --- 6 TONS

CFM (in. wg)

600

900

1200 1400 1600 1800 2000 2200 2400 2600

1 Electric

Heater Module

0.03

0.05

0.07

0.09

0.09

0.10

0.11

0.11

0.12

0.13

2 Electric

Heater Modules

0.13

0.15

0.16

0.16

0.16

0.17

0.17

0.17

0.18

0.18

7.5 --- 8.5 TONS

CFM (in. wg)

2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000

1 Electric

Heater Module

0.03

0.04

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.18

2 Electric

Heater Modules

0.04

0.05

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.15

0.16

0.17

0.19

0.20

General fan performance notes:

1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static

pressure caused by any FIOPs or accessories.

3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories

may add static pressure losses, as shown in Table 20. Selection software is available, through your salesperson, to help

you select the best motor/drive combination for your application.

4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would

work, Bryant recommended the lower horsepower option.

5. For information on the electrical properties of Bryant motors, please see the Electrical information section of this

book.

6. For more information on the performance limits of Bryant motors, see the application data section of this book.

548J