GENERATOR SHUT-DOWN PROCEDURES

NORMAL SHUTDOWN PROCEDURE

To shutdown the generator, use the following procedure:

1. Place both the MAIN, GFCI and LOAD circuit breakers

as shown in Figure 57 to the OFF position.

Figure 57. Main, GFCI and Load

Circuit Breakers Off

2. Place the engine speed switch (Figure 58) in the “LOW

(down) position..

Figure 58. Ignition Switch (Normal)

3. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

WARNING

NEVER stop the engine suddenly except in an
emergency.

CAUTION

ALWAYS make sure the diagnostic switch is placed
in the OFF position before attempting to shut down
the generator. The OFF/RESET switch on the MEC
controller will not shut down the generator if the
diagnostic switch is left in the ON position.

4. Place

the

MPEC Control Switch (Figure 59) to the

OFF/RESET position.

Figure 59. MPEC Control Switch (Off/Reset)

5. Verify that all status LEDs on the MPEC display are

OFF (not lit).

6. Remove all loads from the generator.

7. Inspect entire generator for any damage or loosening

of components that may have occurred during
operation.

EMERGENCY SHUTDOWN PROCEDURE

1. Place

the

MPEC Control Switch (Figure 59) in the

OFF/RESET position.