Generator shut-down procedures – Multiquip DCA150SSJU3 User Manual
Page 54

PAGE 54 — DCA150SSJU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (02/01/10)
GENERATOR SHUT-DOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 57 to the OFF position.
Figure 57. Main, GFCI and Load
Circuit Breakers Off
2. Place the engine speed switch (Figure 58) in the “LOW”
(down) position..
Figure 58. Ignition Switch (Normal)
3. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
WARNING
NEVER stop the engine suddenly except in an
emergency.
CAUTION
ALWAYS make sure the diagnostic switch is placed
in the OFF position before attempting to shut down
the generator. The OFF/RESET switch on the MEC
controller will not shut down the generator if the
diagnostic switch is left in the ON position.
4. Place
the
MPEC Control Switch (Figure 59) to the
OFF/RESET position.
Figure 59. MPEC Control Switch (Off/Reset)
5. Verify that all status LEDs on the MPEC display are
OFF (not lit).
6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening
of components that may have occurred during
operation.
EMERGENCY SHUTDOWN PROCEDURE
1. Place
the
MPEC Control Switch (Figure 59) in the
OFF/RESET position.