PAGE 50 — DCA150SSJU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (02/01/10)

GENERATOR START-UP PROCEDURE (MANUAL)

BEFORE STARTING

The Engine Control Unit (ECU) used with this generator
diagnosis engine faults that arise with the the engine
control system and the engine itself. Engine faults can
be determined by viewing the Diagnostic Trouble Codes
(Active Fault Codes) which are displayed on the Diagnostic
Display Panel located inside the Control Box.

1. Before starting the engine, make sure the diagnostic

switch (Figure 37) on the Diagnostic Display Panel is in
the “OFF” position.

Figure 37. Diagnostic Switch (OFF Position)

2. Place

the

main, G.F.C.I., and aux. circuit breakers (Figure

38) in the OFF position prior to starting the engine.

Figure 38. Main, Aux. and GFCI

Circuit Breakers (OFF)

3. Connect the load to the receptacles or the output

terminal lugs as shown in Figure 12. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup
panel.

CAUTION

The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.

WARNING

NEVER manually start the engine with the main, GFCI
or auxiliary
circuit breakers in the ON (closed) position.

4. Tighten terminal nuts securely to prevent load wires

from slipping out.

5. Close all engine enclosure doors (Figure 39).

Figure 39. Engine Enclosure Doors

STARTING

1. Place

the voltage selector switch in the desired

voltage position (Figure 40).

Figure 40. Voltage Selector Switch

STARTING (MANUAL)

1. Place the engine speed switch (Figure 41) in the LOW

(down) position.

Figure 41. Engine Speed Switch (Low)

2. Place

the

MPEC control switch in the MANUAL

position to start the engine (Figure 42) Observe that
the warning and emergency stop lamps on the
Engine Operating Panel are lit during the initial starting
of the engine. If no abnormal conditions exists, both
lamps will turn off.

Figure 42. MPEC Control Switch

(Manual Position)

INCORRECT

CORRECT