GeNeratOr shUt-DOWN prOCeDUres

normal SHUtdoWn procedUre

To shutdown the generator, use the following procedure:
1. Place both the

main, gFci and load circuit breakers

as shown in Figure 42 to the

OFF position.

Figure 42. Main, Aux. and GFCI

Circuit Breakers (OFF)

2. Let the engine cool by running it at low speed for 3-5

minutes with no load applied.

3. Place the

auto off/reset manual Switch (Figure 43)

in the

oFF/reSet position

Figure 43.

auto off/reset manual

Switch

(Off/Reset)

4. Verify that all status LEDs on the ECU control panel

are

OFF (not lit).

5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of

components that may have occurred during operation.

Warning

never stop the engine suddenly except in an

emergency.

emergencY SHUtdoWn procedUre

1. Push the

Emergency Stop Pushbutton Switch

(Figure 44).

Figure 44. Emergency Stop Button

aUtomatic SHUt-doWn SYStem

This unit is equipped with safety devices to automatically stop

the engine in the event of low oil pressure, approximately

14 psi (97 kPa), or high water temperature, approximately

212°F (100° C), overspeed approximately (2,040 rpm). The

alarm lamps on the ECU illuminate to signify the reason

for the shutdown.