OUtpUt terMiNaL paNeL FaMiLiariZatiON

connecting loads

Loads can be connected to the generator by various

methods, output terminal lugs, camlocks or the convenience

receptacles (Figure 11). Make sure to read the operation

manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,

90A

main circuit breaker is provided. Make sure to switch

all circuit breakers to the OFF position prior to starting

the engine.

Figure 11. Connecting Loads

LOAD

NEUTRAL

GROUND

LOAD

GFCI

RECEPTACLES

LOAD

CS-6369

TWIST-LOCK

RECEPTACLES

U

O

V

AC OUTPUT
TERMINALS

Over Current Relay

An

over current relay (Figure 12) is connected to the main

circuit breaker. In the event of an overload, both the circuit

breaker and the over current relay may trip. If the circuit

breaker can not be reset, the

reset button on the over

current relay must be pressed. The over current relay is

located in the control box.

Figure 12. Over Current Relay

NOTICE

Remember the

overcurrent relay monitors the current

flowing from the

U,o and v output terminal lugs to

the load.
In the event of a short circuit or over current condition,

it will automatically trip the 90 amp main breaker.
To restore power to the

output terminal panel, press

the reset button on the overcurrent relay and place the

main circuit breaker in the closed position (on).