page 24 — dca20SpXU4F Servpro™ • operation and partS manUal — rev. #0 (07/16/14)
OUtpUt terMiNaL paNeL FaMiLiariZatiON
connecting loads
Loads can be connected to the generator by various
methods, output terminal lugs, camlocks or the convenience
receptacles (Figure 11). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
90A
main circuit breaker is provided. Make sure to switch
all circuit breakers to the OFF position prior to starting
the engine.
Figure 11. Connecting Loads
LOAD
NEUTRAL
GROUND
LOAD
GFCI
RECEPTACLES
LOAD
CS-6369
TWIST-LOCK
RECEPTACLES
U
O
V
AC OUTPUT
TERMINALS
Over Current Relay
An
over current relay (Figure 12) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button on the over
current relay must be pressed. The over current relay is
located in the control box.
Figure 12. Over Current Relay
NOTICE
Remember the
overcurrent relay monitors the current
flowing from the
U,o and v output terminal lugs to
the load.
In the event of a short circuit or over current condition,
it will automatically trip the 90 amp main breaker.
To restore power to the
output terminal panel, press
the reset button on the overcurrent relay and place the
main circuit breaker in the closed position (on).