beautypg.com

Memmert HCP 246 Humidity Chambers (Generation 2003) User Manual

Page 27

background image

HCP

page 27

TB approx. 20°C above Tmax

TWW set manually

setpoint temperature

t

°C

controller fault

emergency operation

12.2 Electronic temperature monitor

12.2.1 Overtemperature protection
Adjustment range: up to 10°C max
above nominal temperature (for nominal
temperature see label)

°C

MIN

AUTO

MAX

Using the push/turn control
select the symbol

MAX

.

Hold down the SET key and
set the protection temperature
using the push/turn control.

12.2.2 Undertemperature protection
Adjustment range: from 10°C below
minimum temperature of oven to 10°C
above nominal temperature of oven (for
nominal temperature see label).
The low alarm cannot be programmed
above the value set as high alarm.
Where no undertemperature protection
is required, this has to be set to the
lowest temperature.

°C

MIN

AUTO

MAX

Using the push/turn control
select the symbol

MIN

.

Hold down the SET key and
set the protection temperature
using the push/turn control.

Note:

The temperature monitor can be set independently of the operating mode.
The monitor temperature must always be set sufficiently far above the maximum working temperature.

The manually adjusted monitor temperature

MIN

and

MAX

of the electronic overtemperature protection

is monitored by an adjustable temperature monitor (TWW) Protection Class 3.1 to DIN 12880.

12.2.3 Adjustable temperature monitor (TWW) Protection Class 3.1 to DIN 12 880
If the manually set monitor temperatur

MAX

is exceeded, the TWW takes over the control of the

temperature and starts to control at the monitor temperature. As a warning the symbol is flashing.

If the sounder is switched on in SETUP, the TWW
alarm is additionally signalled by an interrupted
tone. By pressing the SET key the sounder can be
switched off temporarily until the next occurrence
of an alarm event.