Error numbers, causes & remedies
50
2.1 EN - 09/2005
L
8
Appendix
8.1
Error numbers, causes & remedies
Error number
Cause
Remedy
Errors within the DriveServer
E7C18000
Error during download preparation. Repeat
download.
E7C18001
PLC has not stopped.
Stop the PLC program in the target system.
E7C18002
Controller inhibit is not set.
Set controller inhibit in the target system
(e.g. via terminal 28 or code C0040).
E7C18003
Incorrect data type (no LC9 file).
Create new LC9 file.
E7C18004
Check sum check is negative
(faulty check sum).
Restart the download. Increase time-out
time in the system bus configuration tool
(e.g. to 3 seconds).
E7C18005
Item can momentarily not be accessed due to
download.
Repeat download after a few minutes or re-
start your PC.
E7C18006
Target system is momentarily busy copying
RAM blocks.
Start the PLC program in the target system.
E7C18007
Error occurred after the download.
Repeat download.
E7C18008
Error after version comparison during down-
load of an LC7 file.
• Different versions in LC7 file and target
system.
Update the operating system of the 9300 EK.
E7C18009
No template "Cam" in the target system.
Create DDS project based on Template Cam
and transfer it into the target system.