Commissioning
5-8
UONu_^MPMQ
L
5.4.2
Optimisation of control modes
5.4.2.1 Optimisation of motor-current control
Codes required
Code
Name
Possible settings
IMPORTANT
Lenze Selection
Info
C015 V/f-rated
frequency
50.0 7.5
{0.1Hz}
960.0
30.0
{0.1Hz}
960.0
(Software 2x)
(Software 1x)
C021 Slip
compensation
0
0
{1 %}
20
0
{1 %}
12
(Software 2x)
(Software 1x)
C088 Rated motor
current
*
0.0 ... 1.2 ¡ rated output current
* depends on
the unit
Input only
necessary when
motors not
C091 Motor cos
j
*
0.4
{0.1}
1.0
motors not
adapted.
Setting sequence
D
Drives with matching 4 pole standard motors 230/400 V in star connection do not
need to be adapted.After having started the drive, the controller itself detects all
further motor data.
D
The following drives can be optimized by entering the nameplate data ”rated motor
current” and ”cos
j” under C088 or C091:
- Motor one power class smaller than the motor assigned to the controller.
- Motor one or two power classes smaller than the motor assigned to the controller.
- Drives with 2, 6, 8, 10 and 12 pole standard motors.
- Drives with special motors.
D
With the slip compensation C021, you can optimize the ”sensorless speed control”
for your application.
1.If necessary, select
C014 = -4-.
(factory setting)
2.Select V/f-rated
frequency (C015).
Motor voltage
Motor
connection
C015
220/380 V
Y
52,6 Hz
230/400 V, 265/460 V, 280/480 V
Y
50 Hz
220/380 V, 230/400 V, 265/460 V, 280/480 V
D
87 Hz
380/660 V
D
52,6 Hz
400/690 V
D
50 Hz
3.If necessary, enter the
motor data of unadapted
motors (C088, C091).