1 select the control mode, Commissioning – Lenze 8210 series User Manual
Page 42

Commissioning
5-6
UONu_^MPMQ
L
5.4 Optimisation of the operating
characteristic of the drive
_у гЙ~ел зС нЬЙ СзддзпбеЦ лЙннбеЦл узм Е~е беСдмЙеЕЙ нЬЙ ÅìêêÉåíI
нзкимЙ ~еЗ йзпЙк ЕЬ~к~ЕнЙкблнбЕ зк нЬЙ ЕзееЙЕнЙЗ ãçíçêK
vзм Е~е ЕЬззлЙ ДЙнпЙЙе нЬЙ Езенкзд гзЗЙл ÒãçíçêJÅìêêÉåí
ЕзенкздТ ~еЗ ÒsLÑJÅÜ~к~ЕнЙкблнбЕ ÅçåíêçäÒK fе ЕЬ~йнЙк RKQKN узм пбдд
СбеЗ лзгЙ гзкЙ беСзкг~нбзе нз ЬЙдй узм пбнЬ нЬЙ ëÉäÉÅíáçåK
5.4.1
Select the control mode
Code
Name
Possible settings
IMPORTANT
Lenze Selection
Info
C014
¿ Operating mode
-4-
-2- Linear characteristic V~f
d
with
constant V
min
boost
-3- Square characteristic V~f
d
2
with constant V
min
boost
-4- Motor-current control
Control
modes of the
voltage
characteristic
Function
D
Under C014 you can set the control mode and the voltage characteristic.
D
The V/f-characteristic control with auto boost enables a low-loss operation of single
drives with standard three-phase AC motors with load-dependent V
min
boost.
D
The motor-current control enables a ”Sensorless Speed Control”.Compared with the
V/f characteristic control, the drive can operate with a considerable higher torque
and consumes less current during idle running.
C014 = -2-
Linear characteristic
C014 = -3-
Square-law characteristic (e. g. for pumps,
fans)
hPRKMMSR
1 0 0 %
0
0
1
f d
f d N
V m i n
0
0
1
f d
f d N
V m i n
V o u t
1 0 0 %
V o u t
Show/Hide Bookmarks