Technical data – Lenze 8210 series User Manual
Page 15

Technical Data
UONu_^MPMQ
3-5
L
8218
8217
8216
8215
Type
150 % overload
EVF8218-E
EVF8217-E
EVF8216-E
EVF8215-E
Order no.
8218-V003
8217-V003
8216-V003
8215-V003
Type
Variant ”Cold
Plate”
EVF8218-C-
V003
EVF8217-C-
V003
EVF8216-C-
V003
EVF8215-C-
V003
Order no.
Variant ”Cold
Plate”
Motor voltage
3)
V
motor
[V]
0 - 3 × V
mains
/ 0Hz
¼ 50Hz, if required up to 480Hz
Power loss (operation with I
Nx
)
P
loss
[W]
150
200
280
400
Power reduction
[%/K]
[%/m]
40
°C < T
amb
< 50
°C: 2.5%/K
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l: 5%/1000 m
Field
f
Resolution
absolute
0.02 Hz
Field
frequency Digital setpoint
selection
Accuracy
0.05 Hz
Analog setpoint
l ti
Linearity
0.5 % (max. selected signal level: 5 V or 10 V)
Analog setpoint
selection
Temperature
sensitivity
0
¼ 40 °C: +0.4 %
Offset
0 %
Weight
”Cold Plate” without heat sink
”Cold Plate” with heat sink
m [kg]
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
Printed in bold Data for the operation with factory setting and a chopper frequency of 8 kHz.
1)
This power can be additionally obtained when operating a matching motor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here
and 2 minutes base load with 75% I
Nx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
*
Chopper frequency of the inverter
Show/Hide Bookmarks