Electrical installation

Power terminals

4

52

EDKCSEK002 DE/EN/FR 2.0

Cable cross-sections and screw-tightening torques

Cable type

Wire end ferrule

Possible cable
cross-sections

Tightening torque

Stripping
length

Terminal strip X23

rigid

-

0.2 ... 10 mm

2

(AWG 24 ... 8)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb-in)

5 mm

flexible

without wire end ferrule

0.2 ... 10 mm

2

(AWG 24 ... 8)

with wire end ferrule

0.25 ... 6 mm

2

(AWG 22 ... 10)

with TWIN wire end
ferrule

0.25 ... 4 mm

2

(AWG 22 ... 12)

Shielded cables
The following factors decisively determine the effect of the shielded cables:

ƒ

Good shield connection

Ensure a contact surface as large as possible

ƒ

Low shield resistance

Only use shields with tin-plated or nickel-plated copper braids (shields
with steel braids cannot be used).

ƒ

High overlap rate of the braid

At least 70 ... 80 % with 90° overlap angle

The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.