2.7.5
Process controller (L_PCTRL)
Function library LenzeDrive.lib
Special functions
2−80
L
LenzeDrive.lib EN 1.7
Parameter codes of the instances
VariableName
L_PCTRL1
SettingRange
Lenze
nVp
C0222
0.1 ... 500.0
1.0
dnTn
C0223
20 ... 99999 ms
400
nKd
C0224
0.0 ... 5.0
0.0
nVp2Adapt
C0325
0.1 ... 500.0
1.0
nVp3Adapt
C0326
0.1 ... 500.0
1.0
nSet1Adapt
C0328
0.00 ... 100.00 %
0.00
nSet2Adapt
C0327
0.00 ... 100.00 %
100.00
byPCharacteristic
C0329
0 ... 3
0
dnTir
C0332
0.000 ... 999.900 sec
0.000
dnTif
C0333
0.000 ... 999.900 sec
0.000
bBiUnipolar
C0337
0 ... 1
0
Range of functions
·
Control characteristic
·
Ramp generator
·
Value range of the output signal
·
Evaluation of the output signal
·
Deactivation of the process controller
2.7.5.1
Control characteristic
In the default setting, the PID algorithm is active.
Differential component K
d
You can deactivate the K
d
−component by setting nKd = 0.0. The controller now becomes a
PI−controller (or P−controller if the I−component is also switched off).
Integral−action component I
You can switch off the I−component with
·
bIOff_b = TRUE, or on with
·
bIOff_b = FALSE.
Switching on and off can also be done online. If the I−component is to be switched off permanently,
set bIOff_b to TRUE.
Integral−action time T
n
By using nTn you can set the parameter for the integral−action time.