10 dead-band (l_db), Dead−band (l_db), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual
Page 30: Analog signal processing, 10 dead−band (l_db)

2.2.10
Dead−band (L_DB)
Function library LenzeDrive.lib
Analog signal processing
2−20
L
LenzeDrive.lib EN 1.7
2.2.10
Dead−band (L_DB)
This FB eliminates disturbances around the zero point (e.g. interfering influences on analog input
voltages).
L_DB
nIn_a
±32767
nOut_a
nGain
nDeadBand
Fig. 2−19
Dead band (L_DB)
VariableName
DataType
SignalType
VariableType
Note
nIn_a
Integer
analog
VAR_INPUT
nOut_a
Integer
analog
VAR_OUTPUT
The signal is limited to ±32767.
nGain
Integer
−
VAR CONSTANT RETAIN
Gain
nDeadBand
Integer
−
VAR CONSTANT RETAIN
Dead band
Parameter codes of the instances
VariableName
L_DB1
SettingRange
Lenze
nGain
C0620
−10.00 ... 10.00
1.00
nDeadBand
C0621
0 ... 100.00 %
1.00
Function
n D e a d B a n d
n D e a d B a n d
n I n _ a
n O u t _ a
n O u t _ a
n I n _ a
n G a i n = 1 , 0 0
n D e a d B a n d = 6 , 1 0 % = 1 0 0 0
n G a i n = 2 , 0 0
n D e a d B a n d = 0 %
n G a i n
Fig. 2−20
Dead band and gain
·
In nDeadBand you can set the parameters for the dead band.
·
In nGain you can alter the gain.
·
100 % corresponds to 16384.