4 speed preconditioning (l_nset), Speed preconditioning (l_nset), Function library lenzedrive.lib – Lenze DDS Function library Drive User Manual
Page 83: Special functions, Lenzedrive.lib en 1.7

Function library LenzeDrive.lib
Special functions
2.7.4
Speed preconditioning (L_NSET)
2−73
L
LenzeDrive.lib EN 1.7
2.7.4
Speed preconditioning (L_NSET)
This FB conditions the main speed setpoint as well as an additional setpoint (or other signals) for the
subsequent controller structure by using a ramp generator or fixed speeds.
L_NSET
nIEqOHysterisis
32767
*
+
-
/
x/(1-y)
1
0
1
1
0
1
anJogSetValue(1)
anJogSetValue(0)
anJogSetValue(14)
...
0
3
0
15
DMUX
adnTif(1)
adnTif(0)
adnTif(14)
...
adnTir(1)
adnTir(0)
adnTir(14)
...
dnTir
dnTif
0
3
0
15
DMUX
nCInhVal_a
bRfgStop_b
bRfg0_b
bNSetInv_b
nNSet_a
bJog2_b
bJog4_b
bJog8_b
bTI1_b
bTI2_b
bTI4_b
bTI8_b
nSet_a
bLoad_b
bNAddInv_b
nNAdd_a
ramp generator main setpoint
S-shape
main setpoint
nTiSShaped
x
y
byArithFunction
linking main
setpoint and
additional setpoint
nNOut_a
bRfgIEqO_b
CINH
dnTirAdd
dnTifAdd
JOG 0...15
TI 0...15
ramp generator additional setpoint
bJog1_b
1
bExternalCINH_b
bSShapeActive
Fig. 2−73
Speed preconditioning (L_NSET)
Variable name
Data type
Signal type
Variable type
Comment
nCInhVal_a
Integer
analog
VAR_INPUT
Here the signal is applied that the main setpoint
integrator is to accept when the controller is inhibited
(CINH).
bRfgStop_b
Bool
binary
VAR_INPUT
Holding (freezing) of the main setpoint integrator to its
current value.
bRfg0_b
Bool
binary
VAR_INPUT
Leads the main−setpoint integrator via the current
T
i
−times to 0.
bNSetInv_b
Bool
binary
VAR_INPUT
Control of the signal inversion for the main setpoint.
nNSet_a
Integer
analog
VAR_INPUT
Provided for main setpoint; other signals are
permissible.
bJog1_b
Bool
binary
VAR_INPUT
Selection and control of overriding "fixed setpoints"
for the main setpoint.
bJog2_b
Bool
binary
VAR_INPUT
bJog4_b
Bool
binary
VAR_INPUT
bJog8_b
Bool
binary
VAR_INPUT
bTI1_b
Bool
binary
VAR_INPUT
Selection and control of alternative "fixed setpoints"
for the main setpoint.
bTI2_b
Bool
binary
VAR_INPUT
bTI4_b
Bool
binary
VAR_INPUT
bTI8_b
Bool
binary
VAR_INPUT
nSet_a
Integer
analog
VAR_INPUT
Here the signal is applied that the main−setpoint
integrator is to accept when bLoad_b = TRUE.
bLoad_b
Bool
binary
VAR_INPUT
Control of the two ramp generators in special
situations, e.g. quick stop (QSP)
bAddInv_b
Bool
binary
VAR_INPUT
Control of the signal inversion for the additional
setpoint