9parameter reference – Lenze EMF2180IB User Manual
Page 65

Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17
65
9
Parameter reference
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C1230
C1231
C1232
Parameter | Name:
C1230 | Current IP address (display)
Data type: UNSIGNED_32
Index: 23345 = 0x5B31
This code shows the currently active IP address.
An IP address that is altered using code
will only become active after the next mains switching process. Until
then, the currently active IP address differs from the IP address set in
.
Display range
(min. value | unit | max. value)
0
60000
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1231 | Current subnet mask (display)
Data type: UNSIGNED_32
Index: 23344 = 0x5B30
This code shows the currently active subnet mask.
A subnet mask that is altered using code
will only become active after the next mains switching process.
Until then, the currently active subnet mask differs from the subnet mask set in
.
Display range
(min. value | unit | max. value)
0
60000
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C1232 | Current gateway address (display)
Data type: UNSIGNED_32
Index: 23343 = 0x5B2F
This code shows the currently active gateway address.
A gateway address that is altered using code
will only become active after the next mains switching process.
Until then, the currently active gateway address differs from the gateway address set in
Display range
(min. value | unit | max. value)
0
60000
Read access Write access CINH PLC-STOP No transfer