2 led signalling in compliance with dr303-3, Led signalling in compliance with dr303-3, 6commissioning – Lenze EMF2180IB User Manual
Page 46

6
Commissioning
6.4
Initial switch-on
46
Lenze · EMF2180IB communication module (EthernetCAN) · Communication Manual · DMS 5.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.2
LED signalling in compliance with DR303-3
Connection status to the CAN bus with the following signalling:
LEDs
Description
off
Connection to the master is available.
Green
CANopen status ("Z")
Red
CANopen error ("F")
Status display (LED)
Explanation
Constantly red
F: Bus-off
Flicker
Automatic baud rate detection is active.
Blinking green every 0.2 s
Z: Pre-operational, F: No errors
Blinking green every 0.2 s
1 x red blinking, 1 s OFF
Z: Pre-operational, F: Warning limit reached
Green blinking every 0.2 s
2 x red blinking, 1 s OFF
Z: Pre-operational, F: Node guarding event
Constantly green
Z: Operational, F: No errors
Constantly green
1 x red blinking, 1 s OFF
Z: Operational, error: Warning limit reached
Constantly green
2 x red blinking, 1 s OFF
Z: Operational, F: Node guarding event
Constantly green
3 x red blinking, 1 s off
Z: Operational, F: Sync message error
Green blinking every second
Z: Stopped, F: No errors
Green blinking every second
1 x red blinking, 1 s OFF
Z: Stopped, F: Warning limit reached
Green blinking every second
2 x red blinking, 1 s OFF
Z: Stopped, F: Node guarding event