Troubleshooting and fault elimination

9

76

K-HB 13.0001-EN 2.1

9

Troubleshooting and fault elimination

Error message

Cause

Remedy

System parameter

The direction of the specified setpoints

outside the software limit switches, e.g.

positioning behind a limit switch.

Check settings of the software limit

switches.

Homing

No homing has been executed yet,

although a homing mode has been set or is

required (positioning mode).

Check homing settings/execute homing.

Homing

The following homing settings have been

made

z

Reference type: None

z

Reference start: Manually

If no homing is to be executed, no manual

start must be set.

Check homing settings. Select homing

mode or set homing start to power up.

Travel data record

When accessing the bus interface and the

operating program a logic conflict occurs.

Check entries via PROFIBUS and operating

program.