8 parameter numbers, 1 explanation of the parameter numbers, 1 node address ( pnu 918) – Lenze 931W User Manual
Page 51: Parameter numbers, Node address (pnu 918), 8parameter numbers

Parameter numbers
Explanation of the parameter numbers
Node address (PNU 918)
8
51
K-HB 13.0001-EN
2.1
8
Parameter numbers
Parameter numbers defined in the ”Profidrive” PROFIBUS profile
The parameter numbers 900 to 999 are defined or reserved to profile specifications.
Overview of the parameter numbers defined in the ”Profidrive” PROFIBUS profile.
PNU
Meaning
Data type
918
Station address
Unsigned 16
927
Parameter change rights (PCV)
Unsigned 16
928
Control authority (PZD)
Unsigned 16
930
Selection for operating mode
Unsigned 16
947
Fault number
Unsigned 16
970
Load parameters
Unsigned 16
971
Transfer into non-volatile memory
Unsigned 16
Tab. 22
Profidrive parameter numbers
8.1
Explanation of the parameter numbers
The single PNUs, their functions and structure are described in the following paragraph:
How to read the tables
Column
Meaning
PNU
Parameter number
Subindex
Subindex
Description
Description of the parameter number
Lenze
Lenze setting of the parameter number
Selection
minimum value
[smallest increment/unit]
maximum value
Data type
z
Integer 16
z
Unsigned 16
Tab. 23
Explanation of the tables
8.1.1
Node address (PNU 918)
PNU
Subindex Description
Possible settings
Data type
Lenze
Selection
918
0
Station address
Unsigned 16
2
126
Selection Meaning
Description
2 ... 126
After the station address has been changed, the PROFIBUS-DP
interface makes a reset in the drive.