beautypg.com

3 error numbers at response, Error numbers at response, Parameter channel (pcv mechanism) – Lenze 931W User Manual

Page 45

background image

Parameter channel (PCV mechanism)

Job and response processing

Error numbers at response

7

45

K-HB 13.0001-EN

2.1

7.3.3

Error numbers at response

Error number

Information

Detailed description

0

Impermissible PNU

The parameter number is not assigned.

1

Parameter value cannot be

changed

This is a non-writable object, e.g. an actual value.

2

Lower or upper value limit

exceeded

The permissible writable limit range of the object has been

exceeded. Please observe object limits.

3

Faulty subindex

The indicated subindex of the object does not exist or a

format error exists. Check entries.

4

No array

The addressed object is no array type.

5

Wrong data type

The object has been addressed as a wrong data type. See

job identification table.

6

No setting permitted (only

resettable)

No setting permitted (only resettable)

7

Describing element cannot be

changed

Elements such as the serial numbers cannot be changed.

8

PPO - Write requested in the IR is

not available

When installing the hardware a wrong data type was

selected. Please check the HW settings.

9

Description data not available

10

Wrong access group

Access error! The PROFIBUS interface has no parameter

change rights. See PNU 927.

Possible error: Parameter change rights have not been

requested. The operating program and PROFIBUS master try

to access the drive simultaneously. Wrong software

settings in the operating program. (See activation of

PROFIBUS)

11

No parameter change rights

Parameter change rights not requested or access not

possible.

12

Wrong password

A password has been assigned which must be entered for

processing. See password.

13

Text in cyclic traffic cannot be

read

14

Name in cyclic traffic cannot be

read

15

No text array available

16

PPO - Write is missing

When installing the hardware a wrong data type was

selected. Please check the HW settings.

17

Job cannot be executed due to

operating status

Check operating status. Is an error pending at the drive?

Errors can be observed via the software in the online level 1

under Status.

18

Other errors

19 ... 100

Date in the cyclic traffic cannot

be read

Tab. 21

Overview of error messages - job identifications

The error numbers 0 ... 100 are defined or reserved profile-oriented.

This manual is related to the following products: