Commissioning

PROFIBUS communication

GSE file for PROFIBUS connection

5

25

K-HB 13.0001-EN 2.1

5.4

PROFIBUS communication

5.4.1

GSE file for PROFIBUS connection

The device data base file (GSE) for DP slaves (e.g. servo inverter of type 931) contains

characteristic device features of the DP components. Here, it is stored, for instance, which

baud rates and special DP modes are supported by the slave.
Each master needs the corresponding device data base file for a non-ambiguous

identification of slaves on the bus. The GSE file for the servo inverters of the Fluxxtorque

series is attached in the appendix and can also be downloaded from www.Lenze.com.

5.4.2

Hardware configuration

Steps for installing the hardware in the PROFIBUS project:

ƒ

Install the GSE file ”93MW058F.GSE” (version 1.0) according to the settings of the

project planning software for the DP master. After the installation is completed, the

”931_M_W” device appears among the slave nodes.

ƒ

Insert the fieldbus interface module into the PROFIBUS structure using the name

”931_M_W” and assign the PROFIBUS address.

ƒ

Select the process data configuration required for your application ( 26).

ƒ

Indicate the I/O address for the projected data widths.

ƒ

Save the configuration.

ƒ

Expand your user program by the data exchange with the servo inverter.

ƒ

After the project is saved and loaded into the DP master (e.g. an S7 control of the Fa.

Siemens) and the DP master is started, the LED ”Bus-F” of the MFP/MQP should go

off. If not, check the wiring and terminating resistors of the PROFIBUS as well as the

project planning, especially the PROFIBUS address.