7.2 Configuration

settings

In this section the possible settings for the two modules EKS read and EKS write are described. In section 7.3
Connecting the EKS to a PROFINET CPU it is shown, step-by-step, how the device is configured in the
configuration software for the control system.

7.2.1 Properties for the module EKS read

The module EKS read reads alarms and Electronic-Key data and writes this information to the input area of the
control system.

7.2.1.1 Parameter Alarm setting

Here it is defined how alarms that arise during reading are to be handled.

The following settings are possible:

f Activate diagnostics alarm

f Activate process alarm

f Deactivated

7.2.1.2 Parameter Start address

Here you can select a start address from the permissible memory on the Electronic-Key. Possible values on
reading are byte no. 0 to byte no. 116.

7.2.1.3 Parameter Number of bytes

Here you can set the number of bytes to be read. This number of bytes to be read must lie in valid memory on
the Electronic-Key based on the start address. For example with a start address of byte no. 116, the maximum
number of bytes to be read is 8.

7.2.2 Properties for the module EKS write

The module EKS write writes the data from the output area of the control system to the Electronic-Key.

7.2.2.1 Parameter Alarm setting

Here it is defined how alarms that arise during writing are to be handled.
The following settings are possible:
f Activate diagnostics alarm

f Activate process alarm

f Deactivated