2 configuration settings, 1 properties for the module eks read, 1 parameter alarm setting – EUCHNER EKS FSA with PROFINET interface User Manual
Page 28: 2 parameter start address, 3 parameter number of bytes, 2 properties for the module eks write, Manual eks electronic-key adapter profinet
Manual EKS Electronic-Key Adapter PROFINET
Seite 28/44
Subject to technical modifications
109283-01-04/10
7.2 Configuration
settings
In this section the possible settings for the two modules EKS read and EKS write are described. In section 7.3
Connecting the EKS to a PROFINET CPU it is shown, step-by-step, how the device is configured in the
configuration software for the control system.
7.2.1 Properties for the module EKS read
The module EKS read reads alarms and Electronic-Key data and writes this information to the input area of the
control system.
7.2.1.1 Parameter Alarm setting
Here it is defined how alarms that arise during reading are to be handled.
The following settings are possible:
f Activate diagnostics alarm
f Activate process alarm
f Deactivated
7.2.1.2 Parameter Start address
Here you can select a start address from the permissible memory on the Electronic-Key. Possible values on
reading are byte no. 0 to byte no. 116.
7.2.1.3 Parameter Number of bytes
Here you can set the number of bytes to be read. This number of bytes to be read must lie in valid memory on
the Electronic-Key based on the start address. For example with a start address of byte no. 116, the maximum
number of bytes to be read is 8.
7.2.2 Properties for the module EKS write
The module EKS write writes the data from the output area of the control system to the Electronic-Key.
7.2.2.1 Parameter Alarm setting
Here it is defined how alarms that arise during writing are to be handled.
The following settings are possible:
f Activate diagnostics alarm
f Activate process alarm
f Deactivated