2 feedback loop, 3 start, Manual eks electronic-key adapter profinet – EUCHNER EKS FSA with PROFINET interface User Manual

Page 22

background image

Manual EKS Electronic-Key Adapter PROFINET

Seite 22/44

Subject to technical modifications

109283-01-04/10

The switching contact LA1/LA2 is connected to the first input on the safety relay in series with a switching
contact on the enabling switch. The switching contact A100.0 is connected to the second input on the safety
relay in series with the second switching contact on the enabling switch. The result is that these inputs on the
safety relay are only enabled if

f the

EKS-FSA (switching contact LA1/LA2) and

f the control system (switching contact A100.0) issue the related enabling signal and

f the enabling switch is actuated.

The output contacts on the safety relay are enabled only after actuation of the enabling switch.

The safety relay is de-energized without a time delay (stop category 0) and the machine movement is stopped if

f the Electronic-Key is removed or

f the enabling switch is released or

f the machine control system cancels the enable state (contact A100.0 is opened).

Note: The control system output A100.0 may be set only

f if the corresponding Electronic-Key is inserted and

f a suitable operating mode is selected.

6.4.1.2 Feedback loop

The safety relay can be started only with the feedback loop closed. A welded contactor contact in the enable
path will thus be detected when a start request is made and a start is then prevented. The power contactor must
have positively driven contacts.

6.4.1.3 Start

The safety relay start takes place after enabling by the EKS FSA and by the control and after operation of the
enabling switch.