Manual EKS Electronic-Key Adapter PROFINET

109283-01-04/10

Subject to technical modifications

Page 15/44

4.4.2 DIP switch S2

Information!
To be able to define the DCP name using DIP switch S2, all of DIP switch S3 must first be set to OFF.
The usage of the switches to assign the DCP name and the IP address is described in the following in
section

6.1.1.

DCP name

LSB
S2.1

S2.2

S2.3

S2.4

S2.5

S2.6

MSB

S2.7

S2.8

OFF OFF OFF OFF OFF OFF OFF OFF

Apply from

configuration

software*

EKS-PN-1 ON OFF OFF OFF OFF OFF OFF

OFF

EKS-PN-2

OFF ON OFF OFF OFF OFF OFF OFF

EKS-PN-3 ON ON OFF OFF OFF OFF OFF OFF

… … … … … … … … …

EKS-PN-254 OFF

ON

ON

ON ON ON ON ON

EKS-PN-255 ON

ON

ON

ON ON ON ON ON

*) The name that was last set in the configuration software is used (factory setting: all in OFF position)

Information!

If a DCP name is set on DIP switch S2, a name set previously will be overwritten.

4.4.3 DIP switch S3

Using DIP switch S3 you define the way the device is to receive its DCP name.

Function

S3.1

S3.2

S3.3

S3.4

Assign DCP name via configuration software or set via DIP switch
S2.

OFF OFF OFF OFF

Set DCP name via the web interface.

ON

OFF

OFF

ON

Set default IP address

ON

OFF

ON

ON

Internal function, leave switch OFF

OFF

(Factory setting: all in OFF position)

= any switch position

Information!

The usage of the switches to assign the DCP name and the IP address is described in the following in
section 6.1.1.
The IP address is always set automatically via the configuration software and assigned via the DCP
CPU.
To prevent authorized changes to the network, it is sensible to deactivate the web interface after use.
For this purpose DIP switch S3.1 is set to OFF.