4.4.2 DIP switch S2
Information!
To be able to define the DCP name using DIP switch S2, all of DIP switch S3 must first be set to OFF.
The usage of the switches to assign the DCP name and the IP address is described in the following in
section
DCP name
LSB
S2.1
S2.2
S2.3
S2.4
S2.5
S2.6
MSB
S2.7
S2.8
OFF OFF OFF OFF OFF OFF OFF OFF
Apply from
configuration
software*
EKS-PN-1 ON OFF OFF OFF OFF OFF OFF
OFF
EKS-PN-2
OFF ON OFF OFF OFF OFF OFF OFF
EKS-PN-3 ON ON OFF OFF OFF OFF OFF OFF
… … … … … … … … …
EKS-PN-254 OFF
ON
ON
ON ON ON ON ON
EKS-PN-255 ON
ON
ON
ON ON ON ON ON
*) The name that was last set in the configuration software is used (factory setting: all in OFF position)
Information!
If a DCP name is set on DIP switch S2, a name set previously will be overwritten.
4.4.3 DIP switch S3
Using DIP switch S3 you define the way the device is to receive its DCP name.
Function
S3.1
S3.2
S3.3
S3.4
Assign DCP name via configuration software or set via DIP switch
S2.
OFF OFF OFF OFF
Set DCP name via the web interface.
ON
OFF
OFF
ON
Set default IP address
ON
OFF
ON
ON
Internal function, leave switch OFF
OFF
(Factory setting: all in OFF position)
= any switch position
Information!
The usage of the switches to assign the DCP name and the IP address is described in the following in
section 6.1.1.
The IP address is always set automatically via the configuration software and assigned via the DCP
CPU.
To prevent authorized changes to the network, it is sensible to deactivate the web interface after use.
For this purpose DIP switch S3.1 is set to OFF.