System reset to factory settings – EUCHNER MGB-LxxB-PNA-xxx (PROFINET) with Data Structure Type A User Manual
Page 24

Operating Instructions Safety System MGB-L..B-PNA-... (PROFINET)
24
Replacement of an MGB system without program-
ming device
If servicing is required, the MGB system is easy to replace with a new one. For this
purpose the following prerequisites must be met:
Ì
The DIPswitch settings on the new device must match those on the old device.
Ì
Your Profinet master must support the automatic replacement of Profinet sub-
scribers.
Ì
Your Profinet topology must be correctly configured.
Ì
There must be no device name in the MGB system.
This field is empty in the as-delivered state. Systems that already contain a
name must first be reset to the factory settings.
Once these conditions are met, simply replace the old system with the new system.
The Profinet bus does not need to be switched off for this purpose.
System reset to factory settings
You will find detailed instructions in the manual for the configuration software for
your control system.