beautypg.com

Installation instructions, Important – ERICO TDX150 Series User Manual

Page 3

background image

Installation Instructions


34600 Solon Road

HBCR1581 REV4

Solon, Ohio 44139

(440) 248-0100


www.erico.com

IMPORTANT

WARNING. Several “Delta” and “No-neutral” power systems exist and are often confused.
Failure to correctly identify and use the correct SPD may cause an electrical shock or burn hazard.

DESCRIPTION

CONFIGURATION

TYPICAL VOLTAGE

SPD

L3

L1

L2 (B)

G

L3

L2 (High Leg)

L1

N

G

L1

L2

L3

G

L1

N

L2

G

L1

N

L2

L3

G

L1

L2

L3

G

Single Phase
(Split)
1Ø 3W+G

Three Phase Wye
3Ø Wye 4W+G

Three Phase Wye
3Ø Wye 3W+G
(No Neutral)

Three Phase
High Leg Delta
3Ø 4W+G

Three Phase
Grounded Corner
Delta
3Ø 3W+G

("Grounded B Phase")

Three Phase
Ungrounded Delta
3Ø 3W+G

120V

120V

120/240V

L-N
L-G

L-L 240V

240V TDX100 120/240D
TDX150 120/240D

120V 277V 347V

120V 277V 347V

120/208V 277/480V 347/600V

L-N
L-G

L-L 208V 480V 600V

208V 480V 600V

120V 277V 347V

208V 480V 600V

L-L
L-G

240V 480V

0V 0V

240V 480V

L1-G
L2-G
L3-G

L-L 240V 480V

240V 480V

0- 240V 0-480V

240V 480V

L-G

L-L 240V 480V

120V

208V

120V

240V

L1-N
L2-N
L3-N

L-L 240V

120/208V TDX100 120/208
TDX150 120/208
277/480V TDX100 277/480
TDX150 277/480
347/600 TDX100 347/600
TDX150 347/600

208V TDX100 240D
TDX150 240D
480V TDX100 480D
TDX150 480D
600V TDX100 347/600
TDX150 347/600

(1)

(1)

(2)

(2)

(3)

(3)

120/240V TDX100 120/240
TDX150 120/240

240V TDX100 240D
TDX150 240D
480V TDX100 480D
TDX150 480D

Contact Factory

(1)

(2)

(3)

TDXxxx 120/208 can be used, cap neutral. TDXxxx 277/480 can be used, cap neutral. Cap neutral.

This manual is related to the following products: