beautypg.com

Enerpac SafeLink User Manual

Page 5

background image

Input 1 Terminal
(

DI1

)

Input 2 Terminal
(

DI2

)

SLS-3 Only:
Input 3 Terminal
(

DI3

)

Ground Terminal
(

GND

)

Figure 5, Send Unit Terminal Block (SLS-1, SLS-2, SLS-3)

Table 2 - SLS-1, SLS-2 and SLS-3 Wiring information

Input

Function

SEND UNIT Input

Connection Terminal

SEND UNIT Ground

Terminal

Input #1

DI1

GND

Input #2

DI2

GND

Input #3 (SLS-3 only)

DI3

GND

Remove the four screws that secure the face plate of the SLS
send unit. Locate the terminal strip inside the housing. See Figure
5.

Wire the leads from the pressure switch to the

DI1 and ground

terminals per Table 2. Note that the strip contains two ground
(GND) connections. Use whichever one is most convenient. If
more than one pressure switch is used, be sure to connect them
in series.

A position sensing limit switch (if used) can be connected to
terminal

DI2. Or, if desired, this terminal can instead be used to

connect one or more additional pressure switches.

IMPORTANT: Use only limit type position switches. Proximity
type switches are not compatible with the SafeLink system.

Note: For SLS-1 and SLS-2, communication input terminal
DI3 is assigned to a circuit that periodically checks for proper
operation of the sending unit during SafeLink operation. For SLS-
1 and SLS-2, DO NOT make any connections to terminal

DI3.

Terminals

DO1, DO2, DO3, DO4 and DI4 are NOT USED.

7.3 Connecting the 24 VDC Outputs of Receive Unit
SLR-1 or SLR-2 to the Machine Control

Note: This section covers typical connections using the standard
24 VDC I/O machine interface. If using Modbus RTU, Modbus
TCP/IP or Ethernet IP, please refer to sections 9 and 10 of this
manual.

Remove the four screws that secure the face plate of the SLR-1
or SLR-2 receive unit. Locate the receive unit terminal block. See
Figure 6.

PWR
Terminal

Output
Terminals

DO1

-

DO6

Input
Terminals
(not used)

PWR

Terminal

Figure 6, Receive Unit Terminal Block (SLR-1, SLR-2)

Wire the output terminals of the SLR-1 or SLR-2 to the machine
control input terminals. Refer to Table 3 for SLR terminal block
connection information.

Note: Two + 24 VDC power terminals (

PWR) are available at the

top of the terminal block. The

DO-x outputs of the SLR receive

unit are pre-paired to the

DI-x inputs of the SLS send unit.

Table 3 - SLR-1 and SLR-2 Wiring information

Send Unit ID and Input

(SLS-1, SLS-2, SLS-3)

Receive Unit Terminals

(SLR-1, SLR-2)

See Figure 6

ID #

Input #

Output

(-24 VDC)

Power

(+24 VDC)

01

DI1

DO1

PWR

01

DI2

DO2

PWR

01

DI3

*

DO3

* *

PWR

02

DI1

DO4

PWR

02

DI2

DO5

PWR

02

DI3

*

DO6

* *

PWR

8.0 SETUP

8.1 Selecting the Send Unit ID

Open clear round cover on SLS-1, SLS-2 or SLS-3.

Using the rotary switches, set the send unit ID. Start with “01” for
the fi rst send unit in your network. The second send unit would
be “02”. See Figure 7.

Note: The maximum number of send units that can be paired
with a receive unit will vary, depending on the communication
protocol being used. Refer to Section 9 of this manual for
additional information.

Set ID for each
SEND UNIT using
rotary switches.

Figure 7, Setting ID Number of SLS Send Unit

Ground Terminal
(

GND

)

*

SLS-3 only.

* *

SLR-2 only.

5