A
DDRESS LIST
Modbus Programming Manual
38
Version 2
Copyright © 2012 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.
Creating A Profile Header - Request (to instrument)
Field Name
Data
Comments
(Dec)
(Hex)
Profile Name Character 3
A/R
A/R
16 characters of the profile name, e.g. :
A = 65dec / 0x41, B = 66dec / 0x42 etc
a = 97dec / 0x61, b = 98dec / 0x62 etc
Note: Only valid characters from the
instruments supported character set
should be used
The space character (32dec / 0x20hex) is
used to fill any unused characters at the end
of the name.
Characters 9 to 16 are not supported and
should be written to 32dec / 0x20hex
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
32
20
Profile Name Character 10
32
20
Profile Name Character 11
32
20
Profile Name Character 12
32
20
Profile Name Character 13
32
20
Profile Name Character 14
32
20
Profile Name Character 15
32
20
Profile Name Character 16
32
20
Profile Start Signal High Byte
00
00
0 = No delay, 1 = After delay, 2 = At
Time/day
Profile Start Signal Low Byte
A/R
A/R
Profile Start Time (Byte 4 - High)
Floating point number
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Profile Start Time (Byte 1 - Low)
Profile Start Day High Byte
00
00
1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday,
10 = Saturday And Sunday, 11= All Week
Profile Start Day Low Byte
A/R
A/R
Profile Starting Setpoint High
00
00
1 = Current Process Variable Value
Profile Starting Setpoint Low
01
01
Profile Recovery High Byte
00
00
0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint,
4 = Continue profile from where it was when
power failed
Profile Recovery Low Byte
A/R
A/R
Profile Recovery Time (Byte 4 - high)
Floating point number
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Profile Recovery Time (Byte 1 - Low)
Profile Abort action High Byte
00
00
0 = Control to off
1 = Maintain last profile setpoint
Profile Abort Action Low Byte
A/R
A/R
Profile Cycles High Byte
A/R
A/R
1 to 9999 or 10,000 for “Infinite”
Profile Cycles Low Byte
A/R
A/R
Profile Tracks High Byte
00
00
Always set to 1
Profile Tracks Low Byte
01
01
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message Section 2.9.5.9.