2.6. Logger parameters (Data Logger)
2.6.1. Data Recorder
Parameter Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Log Interval
7550
0x1D7E
R/W
0 = Every second
1 = Every 2 seconds
2 = Every 5 seconds
3 = Every 10 seconds
4 = Every 15 seconds
5 = Every 30 seconds
6 = Every Minute
7 = Every 2 Minutes
8 = Every 5 Minutes
9 = Every 10 Minutes
10 = Every 15 Minutes
11 = Every 30 Minutes
12 = Every 60 Minutes
Log Mode
7551
0x1D7F
R/W
0 = Record until memory used
1 = Continues FIFO
Memory
Remaining
7554
0x1D82
R
In Bytes
Time Remaining
7555
0x1D83
R
In seconds
2.6.2. Real Time Clock
Parameter Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Date format
7868
0x1EBC
R
0 = dd/mm/yyyy (European Default)
1 = mm/dd/yyyy (USA Default)
Time
7869
0x1EBD
R/W
In seconds from midnight
Date
7870
0x1EBE
R/W
Day of the week
7872
0x1EC0
R/W
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday