2.4. Control Parameters
Parameter Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Cycle time
4301
0x10CD
R/W
0.5 to 512.0
Control Type
4310
0x10D6
R/W
0 = Single (Heat Only)
1 = Dual (Heat/Cool)
(Only available on Heat Cool Variant)
Control Action
4311
0x10D7
R/W
0 = Direct
1 = Reverse
Proportional Band 1
4312
0x10D8
R/W
0.0 to 999.9
Secondary (Cool)
Proportional Band
4313
0x10D9
R/W
0.0 to 999.9
(Only available on Heat Cool Variant)
Integral/Reset
4314
0x10DA
R/W
0.0 to 5999
Derivative/Rate
4315
0x10DB
R/W
0.0 to 5999
Bias
4316
0x10DC
R/W
For single control 0 to 100, for Duel control -100
to 100
Overlap/DeadBand
4317
0x10DD
R/W
20% of the proportional band
(Only available on Heat Cool Variant)
On/Off Differential
4320
0x10E0
R/W
0.1 to 100
Heat/Primary Power
Upper limit
4321
0x10E1
R/W
10 to 100% Can not be made smaller than
Heat/Primary Lower limit + 10
Heat/Primary Power
Lower limit
4322
0x10E2
R/W
0 to 90% Can not be made larger than
Heat/Primary Upper limit
– 10
Cool/Secondary
Power Upper limit
4323
0x10E3
R/W
10 to 100% Can not be made smaller than
Cool/Secondary Lower limit + 10
Cool/Secondary
Power Lower limit
4324
0x10E4
R/W
0 to 90% Can not be made larger than
Cool/Secondary Upper limit
– 10
Pretune Enable
4325
0x10E5
R/W
0 = Disabled
1 = Enabled
Self tune Enable
4326
0x10E6
R/W
0 = Disabled
1 = Enabled
Loop Alarm Type
4327
0x10E7
R/W
1 = Time
2 = Auto
Loop Alarm time
4328
0x10E8
R/W
1 to 5999
Primary Power
4329
0x10E9
R
0 to 100%
Pretune Status
4332
0x10EC
R
0 = Inactive
1 = Active
Self tune Status
4333
0x10ED
R
0 = Inactive
1 = Active
Loop Alarm status
4334
0x10EE
R
0 = Inactive
1 = Active
Preset Power
4335
0x10EF
R/W
0% to 100%