High limit input parameters – Despatch Protocol 3 Modbus Communications User Manual
Page 14

A
BOUT
T
HIS
M
ANUAL
Modbus Programming Manual
14
Version 2
Copyright © 2012 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.
Parameter Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Filter time
constant
Process Input
Process Variable
1031
0x0407
R
Process Input
Sensor Break
Flag
1032
0x0408
R
0 = Inactive
1 = Active
Process Input
Under Range
Flag
1033
0x0409
R
0 = Inactive
1 = Active
Process Input
Over Range Flag
1034
0x040A
R
0 = Inactive
1 = Active
Process Input
CJC Enable
1035
0x040B
R/W
0 = Enable
1 = Disabled
Process Input
User Calibration
Type
1085
0x043D
R/W
0 = No User Calibration
1 = Single Point Calibration
2 = Two Point Calibration
Process Input
Low Temperature
Calibration Point
1086
0x043E
R/W
Process Input
Low Calibration
Offset
1087
0x043F
R/W
Process Input
High
Temperature
Calibration Point
1088
0x0440
R/W
Process Input
High Calibration
Offset
1089
0x0441
R/W
2.1.2. High Limit Input Parameters
Parameter Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
High Limit Input
Range
9000
0x2328
R/W
Value Range
0
B TC
2
C TC
4
D TC
6
J TC
10
K TC
14
L TC
18
N TC
20
R TC