Condux Deluxe Blower User Manual
Page 8

8
D. OPERATIONAL CAPACITIES
• Pushing Force: 175 lbs (778 N) maximum
• Pushing Speed: 300 ft/min (91 m/min) maximum
• Cable Sizes: .25" to 1.13" (6 mm to 28.7 mm)
• Conduit Sizes: 1/2", 3/4", 1", 1-1/4" TRUE, 1-1/4", 1-1/2" SDR 11 & 13.5,
2" and metric O.D. conduit; 10 & 12 mm, 12.7 mm, 14 mm, 16 mm,
18 mm, 25 mm, 32 mm, 36 mm, 37 mm, 40 mm, 42 mm, 44 mm, 46 mm
and 50 mm
E. ELECTRONIC CONTROL BOx
• Power Requirements: 12 volts DC
• Power consumption is 24 Watts
• Power connection must be to automotive power point or power point
connection on Condux hydraulic power unit
• Fused with a 2.5 amp fuse, 250 volt-5x20mm-GMA type
• Displays: Total Machine Distance, Distance of Run, Operational Speed,
Errors Descriptions
• Automatic Shutdown Speeds: 300 ft/min (91 m/min) maximum
F. PhYSICAL SPECIFICATIONS (DOES NOT INCLuDE LEGS OR jOB BOx)
• Height
16.5" (419 mm)
• Length
30" (761 mm)
• Width
14.8" (375 mm)
• Weight
82 lbs (37 kg)
G. ACOuSTIC EmISSION
• Level of max. sound pressure to the operator seat (ISO 11202) Lep=85 dB(A)
h. CATERPILLAR DRIVE SPECIFICATIONS
• Maximum pushing force: 175 lbs (778 N), depending on cable diameter
• Maximum pushing speed: 300 ft/min (91.5 m/min)
• Maximum clamping force: <114 lbf/in (20 N/mm)
• Independent pushing drive belts with polyurethane pads profiled for cable
0.23" (5.8 mm) to 1.13" (28.7 mm)
• Mechanical gas charged shock absorber clamp to prevent cable crush.
• Side guards.
I. CONDuIT COuPLING REQuIREmENTS
• Must withstand maximum air pressure of 175 psi (12 bar).
• Must withstand axial loading and vibration.
• Must be screw type, compression type, or fusion type.
• Sight Holes must be sealed.
• Must fit snugly.
• Conduit ends must be cut off squarely and deburred.
• Conduit must be fully seated into the coupler.
• Couplers should be installed in a straight section of conduit.
• Must be same size conduit.