Figure 15, A5 download the configuration – CiDRA Use of Foundation Fieldbus Protocol with SONARtrac Transmitters User Manual
Page 43

Double click the AI block in the FBAP window
(If TARGET>MODE_BLK is not OOS, click auto, then OOS quickly to
change TARGET in MODE_BLK to OOS)
On the Process Tab, set CHANNEL to 0x0002
On the Scaling Tab, set L_TYPE to Indirect
Click the Write Changes button
Click Auto button
Close AI window
Double click the SONARtrac AO block in the FBAP window
On the Process Tab, set CHANNEL to 10 (0x000a)
On the Options tab, set SHED_OPT to “normal shed normal
return” (sic)
Click Write Changes button
Click Auto button
Close AO window
A5
Download the Configuration
Click ‘Configure’ on main menu
Select ’Download Configuration…’
Check the ‘Clear Device’ checkbox
Click the ‘Download’ button
Figure 15
Download Configuration