beautypg.com

Maintenance – Aerovent ES-2-06 User Manual

Page 9

background image

Twin City Fan Companies Engineering Supplement 2-06

9

Plug and Plenum fans. These fans are intended for

installation in a user supplied enclosure. Twin City

Fan Companies, Ltd. rarely knows the details of

the enclosure and therefore can not provide guard-

ing based on the needs of the final installation for

these types of fans. The user must verify that the

enclosure a plug or plenum fan is located in is

compliant with EN 953 and EN 294 and EN 811.

Guards shall not be removed during fan operation as

this could cause severe injury. Guards shall not be stood

on or used to support any additional load.

Electrical Supply and Controls

Twin City Fan Companies, Ltd. does not supply elec-

trical controls. Items identified below are intended to

guide the user in supplying controls in conformance to

Annex I of the Machinery Directive and EN 14461:2005

– Industrial Fans – Safety requirements. Furthermore,

electrical installations shall fulfill the requirements of EN

60204-1 and shall be selected for compliance with the

low voltage directive. Those involved with the design

of the electrical supply and control systems should

be familiar with the above mentioned standards and

directives. Control systems including relays, contactors,

Variable Frequency Drive Units, isolating transformers,

over-current and short circuit protection devices may be

required. Relays, contactors, Variable Frequency Drive

Units, isolating transformers, over-current and short

circuit protection devices should all be in compliance

with the Low Voltage Directive. The following is a list

of some of the more common European standards that

are observed when considering compliance with the Low

Voltage Directive.

EN60742

- Isolating Transformers

EN50178

- Electronic Equipment for use in

Power Installations.

EN60730-2-10 - Motor Starting Relays.

EN60947-2-1 - Overload trips.

EN60947-3-1 - Switches, Disconnectors, Switch

Disconnectors and Fuse Combination

Units.

EN60947-4-1 - Electro-mechanical Contactors and

Motor control circuits.

EN60947-5-1 - Electromechanical control circuit

devices.

EN60947-5-5 - Low voltage switchgear and control

gear - Part 5: Control circuit devices

and switching elements - Electrical

emergency stop devices with mechan

ical latching function.

EN61810-1

- Electromechanical elementary relays -

Part 1: General and requirements.

EN60255-23 - Electrical relays - Part 23: Contact

performance.

EN60439-1

- Low Voltage Switchgear and

Switchgear Assemblies, Part 1.

EN 60034

- Rotating Electrical machines Parts 1

and 5.

Variable Frequency Drive Units come under the Low

Voltage and EMC Directives. Standards that shall be

considered for compliance with the EMC Directive are

listed below:

EN 61000-6-4: 2001 Generic Industrial Emission

Standard.

EN 55011:

1998 + A1 Conducted Emissions

Industrial (Group 1 Class A)

In addition, controls shall meet the requirements for

category 2 safety critical control systems as detailed

in EN 954-1. When a VFD is used, controls shall be

implemented to guard against the VFD causing the fan

to run above the maximum safe speed of the fan.

Wiring diagrams provided by the electrical equipment

manufacture shall be followed.

General Considerations for Controls

Intended automatic or remote restart after short term

power failure shall only be permitted if no risk exists

and if there are no other fault conditions.

Warning signs that automatic or remote start may

take place shall be provided when applicable.

After a stop caused by the safety devices indicating

hazardous conditions, restart shall only be possible by

an intentional operation of manual control.

When possible, electrical power cables connected to

fans should be routed where there is least risk of per-

sonnel tripping, walking into or falling over such items

because they have been routed in areas where person-

nel are expected to move.

If it is necessary for periodical inspection and repairs

to override the monitoring and control systems during

operation, then consideration shall be given to the provi-

sion of stand-by fans, motors or other features. This is

allowed provided that:

• The alarm system remains in operation during the

override and an alarm signal is given when the

safety limits are reached.

• Override is indicated by a clearly visible signal.
• Override is affected by auxiliaries specially installed

for that purpose, e.g. key operated switches.

Maintenance

Any maintenance requiring the guards to be removed

shall be performed while the fan is not operating.

When restarting fan after maintenance, follow operation

checklist for start up of fan.

Lockouts shall be used whenever unexpected energiz-

ing of the fan could cause a mechanical or electrical

hazard.

Motor Maintenance

The three basic rules of motor maintenance are:

1. Keep the motor clean.

2. Keep the motor dry.

3. Keep the motor properly lubricated.
Blow dust off periodically (with low pressure air) to pre-

vent motor from overheating.

If the motor is to be started after sitting for more

than a week, the resistance of the motor windings to

earth should be measured (at 500 V DC). If the resis-

tance is less than 10 megohms, the motor should be

dried until a resistance over 10 megohms is measured.

Some smaller motors are lubricated for life. Lubrication

requirements are normally attached to the motor. Use

the motor manufacturer’s recommendations for re-lubri-

cation. If this information is not available, the following

schedule may be used. Motors less than 10 HP running

about eight hours a day in a clean environment should

be lubricated once every five years; motors 15 to 40

HP, every three years. For motors in dusty or dirty envi-

ronments or running 24 hours a day: divide the service

interval by 4. Do not over lubricate. Note that motors

typically use a different type of lubricant than fan shaft

bearings.