5.2. Second level message information (technician)
The second level message information screen is designed for the technician
and will give more information about the current warning/error as well as
simple instructions on what should be evaluated in order to correct the
warning/error.
Press the “return” soft button to exit the second level message information
and return to the standard operating screen.
5.3. List of warning/error messages
MESSAGE
DESCRIPTION
SENTRY RESPONSE
OPERATOR ACTION
Communication
with the engine is
lost
The SENTRY is not receiving
CAN communication for engine
RPM.
No change in operation.
Operator should cancel SENTRY
operation and have engine to
SENTRY communication verified.
Throttle Interlock
Is Not Enabled
The SENTRY’s throttle interlock
is not active when the MODE
button was pressed.
No change in operation.
Operator should activate OEM
interlocking that enables the
SENTRY’s throttle interlock.
Pump Engaged
Interlock Not
Enabled
The SENTRY’s pump engaged
interlock is not active when the
MODE button was pressed.
No change in operation.
Operator should activate OEM
interlocking that enables the
SENTRY’s pump engaged
interlock.
Low Battery
Voltage Fault
The Sentry’s supply voltage is
less than or equal to11.9VDC (12
volt system) or 23.8VDC (24 volt
system).
No change in operation.
Operator should determine the
cause of the low voltage
condition.
Low Battery
Voltage Warning
The Sentry’s supply voltage is
less than or equal to12.4VDC (12
volt system) or 24.8VDC (24 volt
system).
No change in operation.
Operator should determine the
cause of the low voltage
condition.
Low Oil Pressure
Fault
The Sentry has received low oil
pressure diagnostic message
(bus warnings) or the oil pressure
is less than the configured limit
(user warnings).
No change in operation.
Operator should cancel SENTRY
operation and determine the
cause of the low oil pressure
fault.
Low Oil Pressure
Warning
The Sentry has received low oil
pressure diagnostic message
(bus warnings) or the oil pressure
is less than the configured limit
(user warnings).
No change in operation.
Operator should cancel SENTRY
operation and determine the
cause of the low oil pressure
warning.