beautypg.com

Aem ems series 1 / series 2 parameters – AEM 30-4900 Wideband Failsafe Gauge User Manual

Page 13

background image

Page 14

Plot One

Parameter

Description

AFR

Current measured AFR (Gasoline)

AFR Upper Limit

Current upper AFR limit value as set from the Wideband Failsafe Configuration tab

AFR Lower Limit

Current lower AFR limit value as set from the Wideband Failsafe Configuration tab

Plot Two

Parameter

Description

Manifold Pressure

Current measured Manifold Pressure in PSIg

Engine Speed

Current measured RPM, if connected and used



AEM EMS Series 1 / Series 2 Parameters

Below is the Wideband Failsafe related parameter names found in the AEM EMS Series 1 & 2
programmable ECU software when using the AEMNet daisy-chain. Note the slight difference in
nomenclature used with the AEM Wideband Gauge. Use the descriptions listed above for detailed
information.

AEM Wideband Failsafe Gauge Name

AEM EMS Series 1/Series 2 Name

AFR [AFR Gasoline]

WBFS AFR

AFR Upper Limit [AFR Gasoline]

WBFS Up Limit

AFR Lower Limit [AFR Gasoline]

WBFS Low Limit

Manifold Pressure [psi]

WBFS Boost

Engine Speed [rpm]

WBFS RPM

Alarm Status

WBFS Alarm

Alarm Reset Limit [ms]

WBFS Alarm Rst Lmt

Alarm Reset Counter [ms]

WBFS Alarm Rst Cnt

Alarm Delay Limit [ms]

WBFS Alarm Dly Lmt

Alarm Delay Counter [ms]

WBFS Alarm Dly Cnt

Alarm Status

WBFS Status



Plot Three

Parameter

Description

Alarm Source

Indicates what triggered the alarm condition; 3-low AFR condition, 5-high AFR condition, 3-
auxiliary input, 9-alarm test

Alarm Status

Indicates state of alarm; 1-alarm triggered, 0-alarm not triggered

Alarm Reset Limit

Alarm Reset value

Alarm Reset

Counter

Counts up from zero to Alarm Reset value once AFR has returned into the acceptable range

Alarm Delay Limit

Alarm Delay value

Alarm Delay

Counter

Counts up from zero to Alarm Delay value when AFR occurs outside the high or low AFR
limits; once full Alarm Delay value is reached the alarm will trigger; counter will reset back to
zero if AFR returns back into the acceptable range once count up has began