USER OPERATION AND MAINTENANCE

HP SERIES

PORTABLE PUMPS

31

WARNING: TO PREVENT
ACCIDENTAL STARTING
when
servicing the engine or pump
always disconnect the
negative wire from battery
terminal.

1. Place pump on clean work

surface and gain access to the

exhaust primer.

2. Disconnect Negative battery

terminal to prevent accidental

starting of the pump.

3. Unsnap and remove the muffler

heat shield.

4. Disconnect cable from the

actuating lever to the butterfly.

Disconnect all tubing from the

exhaust primer.

5. Remove hex head screws that

hold the exhaust valve to the muffler.

Remove the exhaust valve to a clean

work surface.

6. Place exhaust valve assembly on

bench with ejector body facing up.

Remove hex head screws and

separate the ejector body from the

exhaust valve body.

7. Remove check valve ball from

ejector body.

8. Using wire brush and tip cleaners

carefully remove carbon from ejector

nozzle and check valve assembly.

9. Insert check valve ball into ejector

body. Using a new gasket (P/N

046-0850-01-0) assemble ejector

body to exhaust valve body using

hex head screws.

10. Install exhaust valve assembly to

the muffler using new gasket (P/N

046-6240-01-0) and hex head screws.

11. Connect hoses and cables that

were disconnected back to the

exhaust valve assembly.

12. Ensure priming lever on

instrument panel moves freely after

assembly. If lever does not move

freely the conduit or cable may be

dirty or damaged. Clean or replace

as necessary.

13. Replace the heat shield on the

muffler and snap in place.

14. Reconnect the negative battery

terminal.