USER OPERATION AND MAINTENANCE

HP SERIES

PORTABLE PUMPS

15

the handle must be held in the down

position until the pump is primed.

Once the pump is primed and

pressure is showing on the discharge

pressure gauge the "T" handle is

released and returns to the up

position by spring force for normal

pump operation.

The base "I" version uses a knob

(located above the throttle control)

which is pulled to engage the primer.

5. SUCTION GAUGE: The suction

gauge is located in the center of the

instrument panel and provides the

operator with an indication of the

water pressure on the suction side of

the pump. The suction gauge is a

compound gauge that reads from -1

to 10 BAR (30 in. Hg vac to 150 PSIG).

6. LOW OIL PRESSURE LIGHT (

):

The low oil pressure light is located to

the right of the discharge gauge and

is connected to the oil pressure

switch located on the oil filter

adapter. When the master switch is

first energized the low oil pressure

light will light to indicate the pump

power is on. After the pump starts

and oil pressure builds up the light will

go out to indicate there is sufficient

oil pressure in the engine. The engine

is equipped with an oil pressure

switch that activates the low oil

pressure light when pressure drops to

0.2-0.4 kg/cm

2

(4-6 PSIG). If the light

should light during normal operation

the operator must shutdown the

engine immediately to avoid engine

d a m a g e .

7. CHOKE CONTROL (

): The choke

control is located below the oil light

and is used to control the air fuel

mixture in the carburetor when

starting the engine. Pulling the choke

control out will engage the choke.

After the pump starts pushing in on

the choke control will gradually

disengage the choke and allow

normal operation.

8. DISCHARGE GAUGE: The

discharge gauge is located to the

right of the priming lever and

provides the operator with an

indication of the pump discharge

pressure. The gauge reads from 0 to

28 BAR (0 to 400 PSIG).

9. FUEL PRIMER: The fuel primer is

located on the back side of the

pump engine behind the protective

cover of the HP series pumps. The

fuel system requires priming only

when starting the pump after fuel is

put into the tank initially or if the

pump has run out of fuel. Priming is

accomplished by squeezing the fuel

primer bulb until firm.