Hale HP Series User Manual
Page 19
USER OPERATION AND MAINTENANCE
HP SERIES
PORTABLE PUMPS
19
Insert the bolts and secure in place with
lockwashers and nuts provided.
4. When the pump is mounted and if
access is not provided to fill the fuel tank
install optional fill tube and vent
extension as required.
NOTE: The fuel tank on the HP
series pump is already vented,
therefore a vented fuel cap is
not required
5. Locate and install the instrument
panel on the apparatus. A dimensional
drawing is provided of the instrument
panel to locate the mounting holes.
(NOTE: Approximately 2 meters (6 feet)
of wire and control cables is provided
with the pump. When locating the
instrument panel the installer must take
this into account.) Make electrical
connection from the instrument panel to
the pump with the jumper wires
provided.
6. Connect throttle lever and choke
control to the engine. Secure in place
with the clamps provided. After the
connections are made ensure the
controls work smoothly. There may be
excess cable after the connections are
made. Make a loose coil of the cable
and secure in place with wire ties.
CAUTION: The pump and
motor assembly are vibration
isolated. When making the
permanent connections to the
suction and discharge fittings
DO NOT use hard piping. A
short length of flexible piping is
required to prevent damage
to the pump and engine.
7. Make piping connections to the
discharge flange as required. When
making the piping connections it may
be necessary to turn the pump volute
for proper alignment. To turn the pump
volute:
a. Loosen and remove the "V"-band
clamp using a 1/2 inch or 13 mm
deep well socket.
b. Remove the volute from the
pump body.
c. Locate and remove the
positioning roll pin from the pump
b o d y .
d. Return the volute to the pump
body and install "V"-band clamp.
e. Turn the volute as necessary when
V-BAND CLAMP
TIGHTENING NUT