4 exiting and saving calibration – Hale CAFSPro User Manual
Page 66

❑ Calibration
66
CAFSPro User Operation Manual
p/n: 029-0020-75-0
8.4
EXITING AND SAVING CALIBRATION
To exit calibration and save your set values:
1.
On the CAFSPro display, press and hold the DISPLAY pad. The dis-
play shows PASS then clears. While continuing to hold the DISPLAY
pad, enter the password – (
).
2.
The display shows SCAL for several seconds followed by the standby
(STBY) display.
3.
On the FoamLogix display, press and hold the DISPLAY pad. The dis-
play shows PASS then clears. While continuing to hold the DISPLAY
pad, enter the password – (
).
4.
The display shows SCAL for several seconds followed by the current
water flow value. The FLOW LED also lights.
5.
Shift the pump from PUMP to ROAD, then back to PUMP again. This
resets the system and engages the compressor clutch.
The above procedures complete verification and adjustment of the
CAFSPro system. Before attempting to operate the system disengage
pump (ROAD), as stated in Step 3 above. When the pump is again placed
into service, the Hale CAFSPro system is ready to be activated.