Venting Notes for Figures 34--46

1. For common vent, vent connector sizing and vent

material: United States----use the NFGC Canada----use the

CAN/CSA--B149.1--05

2. Immediately increase to 5--inch (127 mm) or 6--inch (152

mm) vent connector outside furnace casing when 5--inch

(127 mm) vent connector is required, refer to Note 1
above.

3. Side outlet vent for upflow and downflow installations

must use Type B vent immediately after exiting the
furnace, except when KGAVG0101DFG, Downflow Vent

Guard Kit, is used in the downflow position.

4. Type--B vent where required, refer to Note 1 above.
5. Four--inch single--wall (26 ga. min.) vent must be used

inside furnace casing and when the KGAVG0101DFG
Downflow Vent Guard Kit is used external to the furnace.

6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG

required in downflow installations with lower vent

configuration.

7. Chimney Adapter Kit may be required for exterior

masonry chimney applications. Refer to Chimney Adapter

Kit, KGACA02014FC or KGACA02015FC, for sizing
and complete application details.

8. Secure vent connector to furnace elbow with (2)

corrosion--resistant

sheet

metal

screws,

spaced

approximately 180_ apart.

9. Secure all other single wall vent connector joints with (3)

corrosion resistant screws spaced approximately 120_

apart. Secure Type--B vent connectors per vent connector
manufacturer’s recommendations.