WIKA DPT-10 User Manual
Page 49
Proceed as follows:
1
Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
0
.00 %
=
0.0000 bar
0.0000 bar
2
Set the requested value with [+] and [->].
3
Confirm with [OK] and edit the requested bar value.
4
Set the requested bar value with [+] and [->].
5
Confirm with [OK] and move to max. adjustment with [->].
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
The min. adjustment is finished.
Proceed as follows:
1
Edit the % value in the menu item "Max. adjustment" with [OK].
100
.00 %
=
0
.5000 bar
0.0000 bar
Information:
When the instrument is not yet adjusted, then the display pressure for
100 % corresponds to the nominal measuring range of the sensor (in
the above example 500 mbar).
2
Set the requested value with [->] and [OK].
3
Edit the requested mbar value with [OK].
4
Set the requested value with [+] and [->].
5
Confirm with [OK] and move to the menu overview with [ESC].
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
The max. adjustment is finished.
Proceed as follows:
1
Edit the bar value in the menu item "Min. adjustment" with [OK].
Min. adjustment
0
.00 %
DP
-
+
=
0.0000 bar
0.0000 bar
Min. adjustment with
level
Max. adjustment with
level
Min. adjustment with
flow
Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA
49